Recommended testing procedures for self-contained emergency lighting and exit sign luminaires
1. Monthly Procedures
Check that the self-contained emergency lighting and exit sign luminaires function satisfactorily.
Replace any defective lamp(s) or starters if applicable.
2. Yearly Procedures
(a) Operate the self-contained emergency luminaires from the battery supply
unit extinguished due to operation of the automatic low voltage cut-off device built
into the luminaires. Investigate and repair or replace any luminaires which fail
to operate satisfactorily.
(b) Clean all light-emitting-diode and reflecting surfaces
(c) Replace any defective lamp(s).
3. Battery Replacement
The replacement of batterries / cells in self-contained emergency lighting luminaires are recommended
to be carried out in accordance with the following requirements:
(a) Where more than one battery / cells is utilized the complete set of batteries / cell shall be replaced.
(b) Battery / cells removed from one luminaire shall not be used as replacements in another luminaire.
(c) Replacement batteries / cell must all installed or equivalent.